Customization: | Available |
---|---|
Warranty: | One Year |
Display Type: | Digital Only |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model:
|
ES3020
|
ES3020B
|
ES3020E
|
Resistance range:
|
0.01Ω500Ω
|
0.01Ω- 1200Ω
|
0.01Ω-1500Ω
|
Current range:
|
N/A
|
0.00mA-20.0A
|
0.00mA-40.0A
|
Voltage range:
|
N/A
|
N/A
|
0.0V~100V
|
Resistance accuracy:
|
±1%±0.01Ω
|
±1%±0.01Ω
|
±1%±0.01Ω
|
Resistance resolution:
|
0.001Ω
|
0.001Ω
|
0.001Ω
|
Current accuracy:
|
N/A
|
±2%±1mA
|
±2%±1mA
|
Currenty resolution:
|
N/A
|
0.01mA
|
0.01mA
|
Function
|
Ground resistant test, Loop resistance test, leakage current test, grounding voltage test.
|
Ambient temperature and humidity
|
23ºC±5ºC,below 75%rh
|
Range
|
Grounding resistance:0.01-1500Ω ±1%±0.01Ω
|
Current:0.00mA-40.0A ±2%±1mA
|
|
Grounding voltage:0.0V~100V
|
|
Measurement Method
|
Mutual induction
|
Resistance resolution
|
0.001Ω
|
Current resolution
|
0.01mA
|
Clamp Diameter
|
55mm×32mm
|
Clock Function
|
Have
|
Ω+A Synchronized display
|
Ω+A same screen display
|
Display Mode
|
4-digit LCD display, black screen design
|
LCD Dimension
|
46mm×29mm
|
Meter Dimension
|
W/T/H: 85mm×58mmx285mm
|
Sampling Speed
|
About 2 times/second
|
USB interface
|
With USB interface, software monitoring, storage data can be uploaded to the computer, save the print
|
Communication Line
|
USB communication line 1
|
Data Storage
|
500 Groups, the symbol "MEM" gives indication, "FULL" mark will flash to indicate the memory has been full
|
Data Review
|
"MR" symbol indication when reviewing data
|
Overflow Display
|
Exceed measurement range overflow function: "OL " symbol display
|
Interference Test
|
Automatic identify interference signal, "NOISE" symbol indication when the interference current is large
|
Alarm Function
|
Alarm when the measured value exceeds the alarm setting value
|
Battery Voltage
|
Real-time display of battery power, reminding timely charging when battery voltage is low
|
Automatic shut-down
|
"APO" instruction, automatic shutdown after 5 minutes boot
|
Power Consumption
|
50MA Max
|
Weight
|
Instrument: 1180g (with battery)
|
Working Temperature and Humidity
|
-10°C~40C; below 80% rh
|
Insulation Resistance
|
20Ω or more (500V between circuit and outside)
|
Pressure Resistance
|
AC 3700V/rms(between circuit and outside)
|
Suitable for Safety Regulations
|
IEC61010-1(CAT III 300V, CAT IV 150V, Pollution Degree 2); IEC61010-031; IEC61557-1 (grounding resistance)
|
Model
|
ES3020
|
ES3020B
|
ES3020E
|
Earth resistance range
|
0.00Ω~500Ω
|
0.00Ω~1200Ω
|
0.00Ω~1500Ω
|
Current range
|
○
|
0.00mA~20A
|
0.00mA~40A
|
Earth voltage
|
○
|
○
|
○
|
USB data upload function
|
○
|
○
|
○
|
Real-time clock
|
○
|
○
|
○
|
FFT anti-interference technology
|
○
|
○
|
○
|
Data storage
|
○
|
○
|
○
|
Real-time indicator of battery power
|
○
|
○
|
○
|
Backlight
|
○
|
○
|
○
|
Alarm function
|
○
|
○
|
○
|
Battery voltage low indication
|
○
|
○
|
○
|
Overload protection
|
○
|
○
|
○
|
Meter
|
1PC
|
Meter box
|
1PC
|
5# battery
|
4PCS
|
Monitoring Software CD
|
1PC
|
Calibration ring
|
1PC
|
USB communication line
|
1PC
|
Manual, certificate
|
1SET
|
Our Service: